Features:

• Pure sine wave output.Rated power: 1KW to 12KW(12V/24V/48V/96V)
• Big AC Charging current 5-35A,5-40A,5-50A,5-60A(optional)
• Have UPS function AC to DC automatic conversion
• Wide AC voltage& frequency for AC and generator input
• Can adjust battery voltage for different types of batteriesfsuch as Lead-acid battery (default)/Gel battery/Lithium battery.
• DC Start & Automatic Self-Diagnostic function ,5 working modes can choose
(01 City power priority /02 Energy saving /03: Battery priority 04 City power priority Unattended mode /05 Battery priority Unattended)
• High Efficiency Design & “Power Saving Mode” to Conserve Energy
• Smart LCD display and setting(Working modes, Charge Current,Charge Voltage,AC range input, battrty voltage,Battery low voltage shutdown etc.)
• High-low voltage protection,overload, short-circuit Protection under-voltage and over-temperature protection,over voltage,battery reverse connection(optional)etc.
• Support RS485 monitoring function with program,remote monitoring (optional)

Model VH
1000W
VH
1500W
VH
2000W
VH
3000W
VH
4000W
VH
5000W
VH
6000W
VH
8000W
VH
10000W
 VH
12000W
INPUT Rated Capacity 1000W 1500W 2000W 3000W 4000W 5000W 6000W 8000W 10000W 12000W
Peak Power 3000W 4500W 6000W 9000W 12000W 15000W 18000W 24000W 30000W 36000W
Power Range 110VAC:83V-137VAC 120VAC :90 V-150 VAC
220VAC:165V-275VAC 230VAC:173V-287VAC
110VAC:88V-132VAC
120VAC:96V-144VAC
220VAC:176V-264VAC
230VAC:184V-276VAC
AC frequency range 45-65HZ
Efficiency >85%
BATTERY Type Lead Acid battery / GEL battery / Lithium battery
DC Voltage 12VDC/24VDC 24VDC/48VDC 48VDC/96VDC
Input voltage range 12VDC:10.5-15VDC 24VDC:21-30VDC 48VDC:42-60VDC 96VDC:84-120VDC
Floating charge set 12V:12.9 〜13.6 V   24V:25.8V〜27.2V    48V:51.6V〜54.4V   96V: 103.2V〜108.8V
Low voltage restored 12VDC:12.6-14.4VDC 24VDC:25.2-28.8VDC 48VDC:50.4-57.6VDC 96VDC:100.8-115.2VDC
Low voltage shutdown set 12VDC: 10-10.9V       24VDC:20-21.8V    48VDC:40-43.6V  96VDC:80V-87.2V
over voltage protection 12VDC:16.7VDC 24VDC:33.4V 48VDC:66.8V
over voltage alarm 12VDC:15VDC 24VDC:30V    48VDC:60V
AC Charging 5A-35A(40A, 50A, 60A.70A Optional)
OUTPUT Capable of starting
electric motor
0.5HP 1HP 1.5HP 2HP 3HP
AVR Voltage Range 110/120/220/230/240VAC ±110% (Auto-sensing) Without
Power Factor 100%
Transfer Time Typical: 5ms(lncluding detection time)
Temperature Protection >85°C alarm >90°C machine shut off
Overload IPS automatically shut down if overload exceeds 110%-120% of normal value for 30 seconds,
IPS automatically resume work if overload comes to rated load.
Wave form Pure sine wave
Frequency Commercial power supply: shared frequency with the commercial inversion state:60/50±0.5
Output frequency range (electric supply mode) Tracking automatically
Protection Overload, short circuit, battery high and low voltage, AC input high and low voltage protection
Conversion Method Interactive
Temperature Operating Temperature 0°C~70°C
Thermal method Cooling fan in intelligent control<42°C fan rotates slowly to >45°C fan rotates fast
Appearance External Size(mm) (L*W*H) 510*325*215mm 645*325*215mm 765*320*250mm
Gross Size(mm)
(L*W*H)
560*380*280mm 730*400*290mm 840*405*320mm
Net weight(kg) 14 15 18 20 31 34 35 52 54 56
Gross weight(kg) 16 17 20 22 35 37 38 56 58 60
*Product specifications are subject to change without further notice