+86 134 2133 6680

High Frequency Modular UPS RM Plus Series 300 KW-500KW (3 Phase In/3 Phase Out)

Features:

  • 50KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
MODEL RM Plus 300K RM Plus 350K RM Plus 400K RM Plus 500K
Phase 3 Phase in / 3 Phase out
Cabinet Capacity* 300 KW 350 KW 400KW 500KW
Battery  Type Extemal Battery
One Power Module Capacity 50KVA/50KW
Max.   Power Module  No. 6 7 8 10
INPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage Range ’-20%~+15%
Nominal Frequency 50/60Hz(Auto Sensing)
Frequency Range 40Hz~70Hz
Power Factor >0.99  @100%  Load, >0.98@50%  Load
Harmonic  Distortion   (THDi) <4% @ 100%  load
OUTPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage  Regulation(Steady  State) ≤ ±1% Typical (balanced load); ~≤ ±2% Typical (unbalanced load)
Nominal Frequency 50/60Hz
Frequency Range(Synchronized) 46Hz~54Hz or 56Hz~64Hz
Overload Capability 1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion ≤2% THD (Linear Load); ≤4% THD (Non-linear Load)
Eficiency 95.50%
BATTERY / CHARGER
Nominal Voltage ‘+/- 192V~+/- 240V (Selectable)
Maximum Voltage ’+/- 240V (12V×40PCS)
Minimum Voltage ‘+/- 192V(12V×32PCS)
Floating Charge Voltage 2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current
(Per Power Module)
12A (Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm 1065x600x2000 1065x600x2000 1065x1000x2000 1065x1000x2000
Net Weight (Kg) 545 654 932 1020
Power Module (PM-50) Net Weight 44KGS
ENVIRONMENT
Operating Temperature 0~40℃
Relative Humidity 0~95% non-condensing
Altitude* <1000m for Nominal power
IP  Protection IP 20
MANAGEMENT
Smart  RS-232/USB Supports Windows⑧ Family, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
STANDARDS
Safety IEC/EN 62040-1
EMC IEC/EN 62040-2 Category C3
If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.
Product specifcations are subject to change without furher noice.