3 Phase Low Frequency Online UPS LD33 Series 10KVA-600KVA (3 Phase In/3 Phase Out)

HIGH INTELLIGENCE AND RELIABLE POWER SUPPLY

IGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.

SIMPLE TO INSTALL

Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer

MAXIMUM BATTERY CARE

Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.

OTHER CHARACTERISTICS

0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.

MAXIMUM RELIABILITY AND AVAILABILITY

Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)

LOW CONSUMPTION LEVELS

LF33 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.

ADVANCE COMMUNICATION:

RS485/RS232/Dry Contact/SNMP(Optional)

Model 10KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 160KVA 200KVA 250KVA 300KVA 400KVA 500KVA 600KVA
Capacity 8KW 16 KW 24 KW 32 KW  48 KW 64 KW  80 KW 96 KW 128 KW 160 KW 200KW 240KW 320KW 400KW  480KW
INPUT
Rated voltage 400 VAC  Three-Phase
Voltage range 380/400/415VAC(+25%,Can be set through the LCD panel)
Frequency range 40-70Hz(Automatically select synchronization range according to grid frequency)
Range(HZ) 50±5%(±10%) Bypass synchronization tracking
Rectifying pulse number 6 pulse rectification 6/12 pulse rectification 12 pulse rectifier
Phase system 3φ4W+PE(Three phase five wire system)
Battery voltage 384VDC 480VDC
Battery Quantity Standard with 32 Cells(30~34, can be set through the LCD panel)  Standard 40 Cells(38~42 knots,can be set by LCD panel)
OUTPUT
Power factor 0.8/0.9 (Optional)
Voltage(V) L-N: 220±1%   L-L: 380±1%
Three-phase 100% load
unbalance voltage stability
≤2%,Allow 100% imbalance
Frequency(HZ) Normal power, tracking the frequency of power, Grid abnormal. 50±0.2%
Transfer time(ms) 0ms
Parallel operation mode
(parallel type)
Max 8 Parallel
Waveform distortion Linear loadTHD<3% ; Nonlinear loadTHD<5%
Overload capacity 125% full load for 10 minutes, maintain 150 % full load for 1 minute and then switch to bypass power supply,
after reducing the loadcan automatically restore the inverter
Crest factor 3:1
Others
Index Standard with no transfer time maintenance bypass switch
Communication function RS232/RS485/Dry Contact/SNMP (Optional)
Panel display LED displays working status and fault indication; LCD displays three-phase input voltage,
input frequency, three-phase output voltage, load,battery voltage, battery charge and discharge current, etc
Display  7″ Touchable LCD screen display
The audio noise(dB) <65(within 1 meter)
Alarm function Battery low voltage, abnormal power supply, overload, UPS failure, over temperature protection
Protection Input over voltage, battery under voltage, overload, short circuit, over temperature protection
Cooling way Forced cooling
Operating temperature 0℃ to  ~ 40℃
Humidity 0~95%, non-condensing
electromagnetic compatibility Conform GB7260.2
Size(W*D*H)(mm) 540*660*1135 1100*800*1800 800*800*1900 1200*850*1900 2600*1100*2000
Weight 196     233 276 329 461 547.5 643 754 1375 1510 1646
Standard:Conform to GB/IEC regulation: EMC:GB7260.2/IEC62040-2   -GB/17626.2~5/IEC61000-4-2~5   SAFETY:GB4943
Note: Product specifications are subject to change without further notice .